• MNS低压抽出式开关柜
  • MNS低压抽出式开关柜

MNS Low-voltage Draw-out Switchgear

The drawer can be designed as a quarter unit with mechanical interlocking device.
It adopts high strength flame retardant engineering plastic components to reach high safety protection performance.
  • MNS低压抽出式开关柜
Description
Low-voltage Draw-out Switchgear
MNS2.0

Product Introduction

MNS 2.0 is a type tested assembled low-voltage switchgear (TTA) developed and designed by ABB, which complies with standards such as IEC61439 and GB7251.
The installation and connection of the system are carried out in accordance with the IEC364 and DIN VDE0105 standards. Suitable for all places where electricity is generated, distributed, and used.
The MNS 2.0 assembled low-voltage switchgear system has proven its value in the world market after years of use. The entire system fully considers future development opportunities
It can avoid the risk of being eliminated due to technological development.
The cabinet structure adopted by the MNS 2.0 system has a high degree of flexibility, and once the structure is assembled, it no longer needs maintenance. Different standard components can be installed inside the cabinet to meet various usage requirements. Due to the combination design of the entire system, including the electrical structure, this optimized structural design meets the requirements of various components and is suitable for different working environments, achieving corresponding protection levels.

Product features

Compared to traditional products, the MNS 2.0 system has more advantages:
Compact structure, saving cabinet volume;
The cabinet can be arranged back-to-back;
Economical layout of distribution circuits;
All standard components are selected and designed by the convenience process designer;
Full series standardization;
The cabinet can be designed with corresponding protection levels according to the different requirements of work and environment;
Different types of functional components can be installed freely in a cabinet, such as fixed ones
Type components and withdrawable components;
Convenience for equipment updates and improvements;
Equipment operation continuity and reliability;
The safety of operators is guaranteed.

Main technical parameters
Item Technical parameter
Standards IEC61439GB7251JB/T9661
Rated insullation voltage of main circuit (V) AC 660VAC 690V
Rated operating voltage of main circuit (V) AC 380VAC 400V
Rated frequency (Hz) 50 or 60
Rated working current of horizontal main busbar (A) 4006308001000125016002000
2500
400050006300
Rated working current of vertical branch busbar (A) 100~2000
Rated short-term tolerance current of horizontal main busbar (kA) 305080100
Rated peak tolerance current of horizontal main busbar (kA) 63105176225
Protection grade IP30IP40